Shielded Discrete I/O Routing and Shield Termination I/O Module (FTM & Similar, Relay Driver, etc.) in Cabinet  Use shielded cable from MicroNet module to I/O module  Ground cable shield, direct, at MicroNet module and I/O module  Locate I/O Module as close to field I/O cable entry point as possible  Locate I/O module away from analog I/O areas (> 152 mm / 6 inches)  Locate I/O module away from areas with unshielded discrete I/O (>152 mm / 6 inches) Field I/O Cable with I/O Module (FTM & Similar, Relay Driver, etc.) in Cabinet  Route I/O cable against cabinet metal wall/structure from cabinet entry point to I/O module;  If I/O cable is shielded, ground the I/O cable shield, direct, to cabinet at entry point. o If over braid shielded, ground over braid shield to cabinet - connect inner braid shields directly to earth ground at one point only o If single shield, ground shield to cabinet o If field I/O cable shield is grounded direct at remote end of cable, ground the I/O cable shield, capacitively at the entry point to the cabinet  I/O cable shield ground at the I/O module must be the same type as at cable entry point into cabinet, and it should be direct.

I/O Module  not in Cabinet

  Route cable from MicroNet module to I/O module with cable against cabinet metal wall  Ground “MicroNet module to I/O module” cable at entry point to cabinet and at the I/O module Field I/O Cable without I/O Module in Cabinet  Ground I/O cable shield, direct, at the I/O module o If over braid shielded, ground over braid shields to cabinet - connect inner braid shields at I/O module termination point. The Inner braid must still be directly grounded to earth at one point. o If single shield, ground shield to earth at the I/O module  If field I/O cable is grounded direct (DC coupled) at remote end of cable, ground the I/O cable shield capacitively at the I/O module.  I/O cable shield ground at the I/O module must be the same type as at cable entry point into cabinet, and it should be direct connected. 15.2.6.9—Unshielded I/O Unshielded I/O cables may only be used inside the cabinet or for very short distances near the control. Also short on engine sections of discrete inputs & Outputs may be use on the engine/turbine. Discrete I/O is the only I/O type that may be unshielded, for more details on this requirement please see the Discrete I/O MicroNet Module section

I/O Module (FTM & Similar, Relay Driver, etc.) in Cabinet

  Use Shielded cable from MicroNet module to I/O module.  Ground cable direct at MicroNet module and I/O module.  Locate I/O module as close to field I/O cable entry point as possible.  Locate I/O module away from sensitive analog areas (>152 mm / 6 inches) or other types of unshielded I/O. I/O Cable with I/O Module (FTM & Similar, Relay Driver, etc.) in Cabinet  Route I/O cable against cabinet metal wall from entry point to I/O module;  Do not let other cable types within 300 mm (12 inches) of unshielded discrete I/O cables if they are parallel for > 61 cm (2 feet)  Do not let other cable types within 152 mm (6 inches) of unshielded discrete I/O cables if they are parallel for less than 61 cm (2 feet)  Limit length of unshielded I/O cable inside the cabinet. Any length over 61 cm (2 feet) is too long.  If lengths greater than 61 cm (2 feet) are required, special considerations should be used to separate this unshielded wiring from other circuits and minimize electromagnetic RF emissions. I/O Module (FTM & Similar, Relay Driver, etc.) not in Cabinet  Route cable from MicroNet module to I/O module with cable against cabinet metal wall.  Ground “MicroNet module to I/O module” cable at entry point of the cabinet and to the I/O module.

The main products

Spare parts spare parts, the DCS control system of PLC system and the robot system spare parts,

Brand advantage: Allen Bradley, BentlyNevada, ABB, Emerson Ovation, Honeywell DCS, Rockwell ICS Triplex, FOXBORO, Schneider PLC, GE Fanuc, Motorola, HIMA, TRICONEX, Prosoft etc. Various kinds of imported industrial parts

Products are widely used in metallurgy, petroleum, glass, aluminum manufacturing, petrochemical industry, coal mine, papermaking, printing, textile printing and dyeing, machinery, electronics, automobile manufacturing, tobacco, plastics machinery, electric power, water conservancy, water treatment/environmental protection, municipal engineering, boiler heating, energy, power transmission and distribution and so on.