Bailey Controls has a modern training facility available for training your personnel. On-site training is also available. Contact a Bailey Controls sales office for specific information and scheduling. TECHNICAL DOCUMENTATION Additional copies of this manual or other Bailey Controls manuals, can be obtained from the nearest Bailey Controls sales office at a reasonable charge.
The INNIS01 Network Interface Slave Module (NIS) can use the NTCL01 Communication Termination Unit (TCL) for termination. Jumpers on the TCL unit select the type of cable used to connect the NIS module to an INFI-NET system. Refer to the NTCL01 instruction for complete information. Figure A-1 shows the location of jumpers and connectors. Figures A-2 and A-3 show the coaxial and twinaxial cable connections. Table A-1 lists the jumper settings used on TCL unit circuit board revision levels D and E. Table A-2 lists the jumper settings used on TCL unit circuit board revision levels F or higher.
INTRODUCTION
The INNIS01 Network Interface Slave Module (NIS) can use the NICL01 Communication Termination Module (ICL) for termination. Jumpers on the ICL module select the type of cable used to connect the NIS module to an INFI-NET system. Refer to the NICL01 instruction for complete information. Figure B-1 shows the location of jumpers and connectors. Figures B-2 and B-3 show the coaxial and twinaxial cable connections. Table B-1 lists the jumper settings used on ICL module circuit board revision level C. Table B-2 lists the jumper settings used on ICL module circuit board revision levels D or higher.
The INICT01 INFI-NET to Computer Transfer Module
(ICT) uses the NIMF01 Multi-Function Controller Termination Module for termination. The NIMF02 Multi-Function Controller Termination Module is required when terminating redundant interfaces. The dipshunt configurations shown in Figures D-1, D-2, D-3, and D-4 apply to both NIMF01 and NIMF02 modules Figure D-1 shows the dipshunt configuration required when connecting an ICT module (DCE) directly to the host computer (DTE). Figure D-2 shows the dipshunt configuration required when connecting an ICT module (DTE) to a modem (DCE). Figure D-3 shows the dipshunt configuration required to interface to a mainframe computer (VAX). Figure D-4 shows how to configure the IMF unit so that port 2 can drive a diagnostics terminal. Figure D-5 shows the RS-232-C signals and the associated DB-25 connector pin assignments. Refer to the NIMF01 and NIMF02 instruction for complete information.
Spare parts spare parts, the DCS control system of PLC system and the robot system spare parts,
Brand advantage: Allen Bradley, BentlyNevada, ABB, Emerson Ovation, Honeywell DCS, Rockwell ICS Triplex, FOXBORO, Schneider PLC, GE Fanuc, Motorola, HIMA, TRICONEX, Prosoft etc. Various kinds of imported industrial parts
Products are widely used in metallurgy, petroleum, glass, aluminum manufacturing, petrochemical industry, coal mine, papermaking, printing, textile printing and dyeing, machinery, electronics, automobile manufacturing, tobacco, plastics machinery, electric power, water conservancy, water treatment/environmental protection, municipal engineering, boiler heating, energy, power transmission and distribution and so on.