Hardware failure on NMBA module. Switch power off and wait a few seconds before switching the power on again; if the problem persists, check that fieldbus parameter 02 MODBUS MODE is set to RTU wdg:rst.Continuous reboot. Fast blinking of ERROR LED for approx. 2 sec. repeated every few sec. Drive configuration write failed (DDCS link communication fault). Check fibre optics, DDCS channel and SW version of the drive.Size of the Link: 2 stations (3 to 248 in Multiple Drive Control) Medium: Fibre optic cable • Construction: Plastic core, diameter 1 mm, sheathed with plastic jacket • Attenuation: 0.31 dB/m • Maximum Length between Stations: 10 m
Fieldbus Link
Compatible Devices: Any Modbus device capable of Modbus communication as a master. Size of the Link: 247 stations including repeaters (31 stations and 1 repeater per segment) Medium: Shielded, twisted pair RS485 cable • Termination: built in the NMBA-01 Module • Modbus cable: Belden 9841 (typical) • Maximum Bus Length: 1200 m Topology: Multi-drop Serial Communication Type: Asynchronous, half Duplex Transfer Rate: 1200, 2400, 4800, 9600, 19200 bit/s Protocol: Modbus
NMBA-01
Enclosure: Plastic, dimensions 45 × 75 × 105 mm; degree of protection IP 20 Mounting: Onto a standard mounting rail Settings: Via drive interface (control panel) Current Consumption: 65 mA at 24 V d.c. Connectors: • Light transmitter (grey) and receiver (blue) (Hewlett-Packard Versatile Link) for connection to the drive • One Combicon MVSTBW 2,5/8-ST-5,08 (8-pole, cross-section 2.5 mm2 max.)• All materials are UL/CSA approved • Complies with EMC Standards EN 50081-2 and EN 50082-2