LOM Action Delay 

• Sets Time Delay for LOM Action to begin once Loss of Mains is detected. 

• Delay time From LOM detection to mains breaker open, and engine start command. 

• In applications where the utility bus is somewhat unstable, this setting can be used to prevent momentary disruption of the mains frequency or voltage on from causing unwanted Loss of Mains actions to occur.

Automatic Sequencing

 • Enables or Disables Auto Sequencing for that unit. o Disabled and in AUTO(Discrete Input #1) ƒ Will start on Loss of Mains ƒ Does not start when Master Unit is put in the AUTO and Run w/Load mode 

• Disabling at the master disables all auto sequencing

Automatic Sequence Delay

 • Amount of time in seconds before Auto Sequencing begins.

 • Delay time starts when the Master unit closes its generator breaker. 

• This insures that all generator sets have ample time to synchronize and close to the bus prior to load being added or generator sets being sequenced back offline. 

• Only functions if Auto Sequencing is Enabled

Maximum Generator Load 

• % system load on all units with gen breakers closed, and on the same network, in Auto, and in Load Sharing or Process control modes, at which active master unit will begin timing to sequence next unit on line.

 • Consult Chapter 5, Generator Sequencing, for details. Next Genset Delay 

• Period of time that will pass before master auto sequences an additional generator on line after the Maximum Generator Load Set Point is exceeded, and remains exceeded.

 • Delay is effective only in active master unit.