CT Phase A Scale
• Calibrates CT Phase A o Do NOT calibrate if generator load is under 50% of Rated. o Factory calibration will be within 1%.
• Load generator to above 50% of Rated load
• Measure actual generator currents with clamp on ammeter or panel ammeter.
• Adjust until monitored current equals measured current.CT Phase B Scale
• Calibrates CT Phase B o Do NOT calibrate if generator load is under 50% of Rated. o Factory calibration will be within 1%.
• Load generator to above 50% of Rated load
• Measure actual generator currents with clamp on ammeter or panel ammeter.
• Adjust until monitored current equals measured current.
Bus PT Scale
• Calibrates Mains/ Bus PT input.
• This input can be calibrated using the Mains Pt or the Bus PT.
• Mains PT calibration o Measure the Mains voltage o Adjust scale until Mains monitored voltage equals the mains measured voltage.
Bus PT calibration o Measure the Bus voltage. If the BUS is dead no calibration can be done. o To get the EGCP-2 to switch from monitoring the Mains to monitoring the Bus, the generator must be started. Configure Synchronizer Mode for CHECK Close Discrete inputs AUTO and Run w/Load to start engine. Adjust Bus PT Scale until monitored voltage equals measured voltage
Synchronizer
• Calibrates phase angle error detection of EGCP-2. • Factory calibrated for zero phase angle error between bus and mains A phase (depending on synchronizing operation) and A phase generator inputs. • With synchronizer in “check” mode, and a live bus, monitor the synchroscope menu of the EGCP-2 for “phase angle”. • Monitor Voltage across open gen contactor/breaker or panel synchroscope for phase angle error between generator and bus. • Adjust synchroscope calibration for lowest voltage across gen breaker, or 12 o’clock reading on panel mounted synchroscope.