Spare parts spare parts, the DCS control system of PLC system and the robot system spare parts,
Brand advantage: Allen Bradley, BentlyNevada, ABB, Emerson Ovation, Honeywell DCS, Rockwell ICS Triplex, FOXBORO, Schneider PLC, GE Fanuc, Motorola, HIMA, TRICONEX, Prosoft etc. Various kinds of imported industrial parts
The EnerVista PQMII Setup Software will notify the user when the PQMII has finished loading the file. Z Carefully read any displayed messages and click OK to return the main screen. If the PQMII does not communicate with the EnerVista PQMII Setup Software, ensure that the following PQMII setpoints correspond with the EnerVista PQMII Setup Software settings: MODBUS COMMUNICATION ADDRESS BAUD RATE PARITY (if applicable) Also, ensure that the correct COM port is being used. 4.3.4 Loading Saved Setpoints Z Select the previously saved setpoints file from the File pane of the EnerVista PQMII Setup Software main window. Z Select the setpoint file to be loaded into the PQMII. Z Click OK. Z Select the File > Edit Settings File Properties menu item and change the file version of the setpoint file to match the firmware version of the PQMII. Z With the updated setpoint file selected in the File pane, select the File > Write Settings to Device menu item and select the target PQMII to receive the previously saved settings file. A dialog box will appear to confirm the request to download setpoints. Z Click Yes to send the setpoints to the PQMII or No to end the process. The EnerVista PQMII Setup Software will load the setpoint file into the PQMII. If new setpoints were added in the firmware upgrade, they will be set to factory defaults
The System Setup page will be used as an example to illustrate the entering of setpoints.
When a numeric setpoint such as PHASE CT PRIMARY is selected, EnerVista PQMII Setup Software displays a keypad that allows the user to enter a value within the setpoint range displayed near the top of the keypad:Z Click Accept to exit from the keypad and keep the new value. Click on Cancel to exit from the keypad and retain the old value. Z In the Setpoint / System Setup dialog box, click on Store to save the values into the PQMII. Z Click OK to accept any changes and exit the window. Z Click Cancel to retain previous values and exit.
Viewing Actual Values If a PQMII is connected to a computer via the serial port, any measured value, status and alarm information can be displayed. Use the Actual pull-down menu to select various measured value screens. Monitored values will be displayed and continuously updated. 4.4.3 Setpoint Files To print and save all the setpoints to a file follow the steps outlined in 4.3.2: Saving Setpoints to a File. To load an existing setpoints file to a PQMII and/or send the setpoints to the PQMII follow the steps outlined in 4.3.4: Loading Saved Setpoints. 4.4.4 Getting Help A detailed Help file is included with the EnerVista PQMII Setup Software. Select the Help > Contents menu item to obtain an explanation of any feature, specifications, setpoint, actual value, etc. Context-sensitive help can also be activated by clicking on the desired function. For easy reference, any topic can be printed by selecting File > Print Topic item from the Help file menu bar.