The figures on the following pages give the key dimensions for use in physically mounting the product. When mounting multiple drives in a row some customers have found the stiffness of the drive and their mounting panel to be too low. To increase the mounted mechanical integrity, connect to the threaded insert on the top front edge. The overall drive panel dimensions and the mounted depth not including mating connectors is listed in the below chart. The extra depth for mating connectors is 1.0" or less.
Connecting to AC Power
The PC800 series drives are functionally compatible with all standard forms of three phase ac lines: • Grounded neutral WYE
• Open-Delta Grounded Leg
• TEE AC Power The AC power source for connector TB1 (control power supply) can be either single phase 115-240 VAC referenced to neutral (PE) or a symmetrical 115-240 VAC to neutral. Fusing Use slow blow fuses in series with TB1 pins 1, 2, and 3 as shown in the figure on pages D-7.
Connection to PE Ground
TB1-3 must be connected to Protective Earth ground (this pin is marked with the PE symbol). The connection at the Protective Earth ground end must be hard wired (not utilize pluggable connections) A ground fault detector (RCD) can not be depended upon for safety.