Spare parts spare parts, the DCS control system of PLC system and the robot system spare parts,
Brand advantage: Allen Bradley, BentlyNevada, ABB, Emerson Ovation, Honeywell DCS, Rockwell ICS Triplex, FOXBORO, Schneider PLC, GE Fanuc, Motorola, HIMA, TRICONEX, Prosoft etc. Various kinds of imported industrial parts
Products are widely used in metallurgy, petroleum, glass, aluminum manufacturing, petrochemical industry, coal mine, papermaking, printing, textile printing and dyeing, machinery, electronics, automobile manufacturing, tobacco, plastics machinery, electric power, water conservancy, water treatment/environmental protection, municipal engineering, boiler heating, energy, power transmission and distribution and so on.
Manual Override in the ON Position When a manual override of the …R824 Relay Output Module is set to the “ON” position, the following applies: • If the relay output has been configured, its logical state will depend upon the actual output configuration. • If the relay output is unconfigured, it will be switched ON. • Regardless of configuration, the feedback signal on the LONWORKS network: nvoDoActPosnFb[ ] will have a value of 1000…0% and a state of -1. • Regardless of configuration, the status LED (yellow) will flash to indicate “manual override.” Manual Override in the OFF Position When a manual override of the …R824 Relay Output Module is set to the “OFF” position, the following applies: • If the relay output has been configured, its logical state will depend upon the actual output configuration. • If the relay output is unconfigured, it will be switched OFF. • Regardless of configuration, the feedback signal on the LONWORKS network: nvoDoActPosnFb[ ] will have a value of 0% (direct) or 100% (reverse) and a state of -1. • Regardless of configuration, the status LED (yellow) will flash to indicate “manual override.”
• Type: XFR825 Floating Output Module • Housing: light-gray • Floating outputs sufficient for driving up to 3 floating actuators • Manual overrides and 3 corresponding pairs of status LEDs In the event of communication problems, the three floating outputs will move to the safety positions you have configured in CARE, see floating output point description in the CARE – User Guide, EN2B-0182GE51 / 74-5587.In the case of voltages above 30 VAC/DC and if inductive components are to be connected to relays switching more often than once every 2 minutes, these components must be prevented from causing harmful interference to radio or television reception (conformance with EN 55014). • Max. voltage for UL 864-compliant applications is 24 V.
Manual Override in the AUTO Position When a manual override of the XFR825 is set to AUTO, the following applies: • The output signal of the respective floating output (R1 + R2 or R3 + R4 or R5 + R6) will be as commanded. • The respective pair of status LEDs will be ON/OFF as commanded. Manual Override in the Override Position (0…100%) When a manual override of the XFR825 is set to 0…100%, the respective floating output will drive to the set position. The runtime depends upon the actuator runtime configured in CARE and on the actual position.