ADEPT 10332-31150 gateway module
Connect the unit’s actuator wires to the control’s actuator driver output on terminals 13(+), 14(–), and 15(shield). This output’s current range is software configurable and can be programmed to output a drive current of 0–200 mA, 20–200 mA, 4–20 mA, or 0–20 mA. Do not connect the shield wire to the actuator or any other point. Verify that the output’s shield wire has continuity its entire distance to the actuator and is insulated from all other conducting surfaces.
Analog Inputs
Connect input wiring to terminals 19(+), 20(–), and 21(shield) to use Analog Input #1 and connect input wiring to terminals 22(+), 23(–), and 24(shield) to use Analog Input #2. These Analog Inputs are software configurable to function as one of the following options: Remote Speed Setpoint Monitor Signal Synchronizer Bias Signal Input (–2.5 to +2.5 Vdc signal) Process Setpoint Process Signal