1 Not in overspeed test mode, Raise Speed discrete input is closed, Lower Speed discrete input is closed, Run discrete input is closed. 2. If remote is selected, and the turbine is started, the speed reference will ramp at the Remote Setpoint Fast Rate. 3. If remote is not selected, the speed reference will ramp at the Idle to Rated Rate.
If the turbine is running
and Remote Control is selected, the speed reference will ramp to the Remote Speed Setpoint. Found in F**Remote Speed Control. 5. As the analog input, remote speed input is changed, the speed reference will ramp up or down at the Remote Setpoint Slow Rate unless the difference between the setpoint and the actual speed is greater then the Remote 2nd Deadband. At this point the ramp will change to the Remote Setpoint Fast Rate until the deadband is met. 6. If the analog input USE INPUT #X FAIL TRIP is set TRUE and if the input goes less then 2 mA or greater the 22 mA, the control will shut down.