The current through the transformer primary should be approximately 6mA. If the measured current is zero, suspect an open circuit primary winding, series resistor or connection. If the measured current exceeds 8mA, check that the external dropper resistors are correctly fitted (380/440V version only). Also check that the series resistor R11, fitted on the PCB is the correct value. If these are correctly fitted, then the primary windings may be shorted together – return the module for repair.
Warranty: 365 days Goods status: new/used Shipping method: Courier delivery
Company product range
----------------------Ruichang Mingsheng Automation Equipment Co., Ltd----------------------
PLC module, programmable controller, CPU module, IO module, DO module, AI module, DI module
Network communication module,
Ethernet module, motion control module, analog input module, analog output module, digital input module, digital output
Module, redundancy module, power module, relay output module, relay input module, processor module
Calibration information
All relays are supplied precalibrated. The 380/440V ac version of the MVTD 12 is calibrated with the external series dropper resistors, Rext 2, fitted on the resistor assembly supplied with the module. If any external ac series resistor or the printed circuit board assembly itself is exchanged, the relay will require recalibration. The dc series dropper resistor Rext 1 may be exchanged without affecting the relay calibration.